|
This Web page allows you to set security options and can only be
accessed in Security Access Mode. You must perform a Security Access Reset
to enter Security Access Mode. To perform a Security Access Reset, follow
these steps:
1. Remove the i.LON 600 LonWorks/IP Server from the TCP/IP
network and attach it directly to a computer using an Ethernet cable or a
local server hub. This step is optional but recommended since performing a
Security Access Reset will temporarily reset the i.LON 600
LonWorks/IP Server's IP address to 192.168.1.222. You may also need to assign
a static IP address to your PC, since your PC will not be able to obtain
an IP address from DHCP in this configuration.
2. Press and hold the Service pin on the i.LON 600 LonWorks/IP
Server using a ballpoint pen or similar device.
3. Reboot the i.LON 600 LonWorks/IP Server while still holding
down the Service pin. This can be done from the Reboot Web page (see
Rebooting the i.LON 600 LonWorks/IP Server, later in the user’s
guide), by using the Reboot command in the Console Application, or by
pressing the Reset button (just to the left of the LAN LEDs).
4. All the LEDs will light for about two seconds. Continue holding the Service pin.
At this point this both the Power and Service LEDs will begin to blink rapidly.
5. Approximately 10 seconds from when the reboot began, the Service LED
will illuminate solid orange. At this point you can release the Service pin.
The i.LON 600 LonWorks/IP Server will now be in Security Access
Mode. Its IP address, subnet mask, and gateway are temporarily changed to
192.168.1.222, 255.255.255.0, and 192.168.1.222, respectively. They are
changed back to the values specified on the Setup and Security Web pages
once the i.LON 600 LonWorks/IP Server exits security access mode
(i.e. when the i.LON 600 LonWorks/IP Server is rebooted). This IP
address change may place the i.LON 600 LonWorks/IP Server on a
subnet that your computer cannot communicate with. In order to communicate
with the i.LON 600 LonWorks/IP Server after a Security Access Reset,
you can either modify your computer's IP configuration to place it on the
192.168.1.* subnet or enter the following command using the Windows Command
Prompt:
route add 192.168.1.0 mask 255.255.255.0 %COMPUTERNAME%
This command allows your computer to communicate with the i.LON
600 LonWorks/IP Server even when they are not on the same subnet. This
command does not persist through computer reboots, but you can add it to
the startup script of your computer.
When in Security Access Mode, you can access the Security and the
Restore Factory Defaults Web pages. The i.LON 600 Web server is
always enabled in Security Access Mode regardless of whether the Enable
Web Server checkbox is set.
FTP User Name
Enter the user name to be used for FTP access. The user name
can be up to 20 characters long and may contain letters, numerals, and the
underscore character.
FTP Password
Enter the password to be used for FTP access. The password
can be up to 20 characters long and may contain letters, numerals, and the
underscore character. The password will be displayed as all asterisks.
Re-enter Password
Reenter the password from the FTP Password value.
Since the password is not displayed, this prevents an incorrect password being
set due to a typing error.
Enable FTP
If this option is checked, the i.LON 600 LonWorks/IP Server will respond to FTP requests.
Enable Web Server
If this option is checked, you will be able to access the i.LON
600 LonWorks/IP Server via HTTP. If this is disabled, you will not be able
to access the i.LON 600 LonWorks/IP Server through HTTP until a security
access reset is performed. The i.LON 600 Web
server is always enabled in Security Access Mode regardless of whether the Enable
Web Server checkbox is set. If you change this option, you must
reboot the i.LON 600 LonWorks/IP Server for this change to take
effect.
Enable access to Security and Factory Defaults pages without Security Access Reboot
You must first perform a Security Access Reset to enable this feature.
If this checkbox is checked, then you can access this security page (and
its settings) without first performing a Security Access Reset.
Enable remote reboot
If checked, this feature allows you to reboot an i.LON 600
LonWorks/IP Server without having physical access to it (i.e., without
depressing the Reset button). If this checkbox is not checked, the reboot
Web page will be disabled.
MD5 Authentication
You can enter an MD5 authentication key for use with the LonWorks/IP Configuration Server.
If authentication is enabled in the LonWorks/IP Configuration Server,
the MD5 key entered there must match the key entered here.
|